Sign In | Join Free | My benadorassociates.com
China Shenzhen Zhong Jian South Environment Co., Ltd. logo
Shenzhen Zhong Jian South Environment Co., Ltd.
We are one of the first high-tech enterprise in the industry that provides technical solutions for air pollution control and treatment.
Verified Supplier

2 Years

Home > FFU Fan Filter Unit >

Different Sizes FFUs Refer To Different Application Scenarios And Technical Requirements

Shenzhen Zhong Jian South Environment Co., Ltd.
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now

Different Sizes FFUs Refer To Different Application Scenarios And Technical Requirements

Brand Name : ZJNF

Model Number : FFU 4X2

Certification : CE

Place of Origin : China

MOQ : 1

Price : negotiate

Payment Terms : tt lc PayPal credit card

Delivery Time : 18 days

Packaging Details : plywood/wooden package

Product Name : 403 Forbidden

Server : openresty

Status Code : 403

Description : The server understood the request, but is refusing to fulfill it.

Contact Now

Application Scenarios and Technical Requirements for FFUs with Different Sizes

1. Standard Size (1175×575mm)

  • Application‌: General cleanroom environments (ISO Class 5-8) in electronics manufacturing and standard laboratories.
  • Technical Parameters‌: Airflow 1000 m³/h, wind speed 0.45 m/s ±20%, noise ≤55 dB, power 120 W.
  • Features‌: Compatible with mainstream ceiling grid systems, cost-effective, suitable for large-scale cleanroom modular layouts.

2. Large Size (1175×1175mm)

  • Application‌: Ultra-clean environments for advanced semiconductor manufacturing (e.g., 5nm production lines) and lithography equipment (ISO Class 1-2).
  • Technical Parameters‌: Airflow 2200 m³/h, ULPA efficiency 99.9995% @ 0.12μm, with variable frequency speed control.
  • Features‌: Requires liquid-sealed design for airflow uniformity (0.45 m/s ±5%).

3. Custom Non-Standard Sizes

  • Application‌: Special cleanroom booths or unique industrial equipment (e.g., explosion-proof facilities).
  • Technical Parameters‌: Customized based on requirements, materials available in explosion-proof stainless steel or aluminum.
  • Features‌: Requires additional evaluation of static pressure (≥140 Pa) and harmonic interference issues.

Selection Recommendations

  • Electronics/Food Industry‌: Prioritize standard sizes for cost-effectiveness and compatibility.
  • Semiconductor/Pharmaceutical Industry‌: Choose high-static-pressure or ULPA-filtered medium/large FFUs.
  • Special Environments‌: Custom designs must consider material (e.g., S304 stainless steel) and explosion-proof requirements.

Product Tags:

FFU fan filter unit sizes

      

FFU application scenarios

      

FFU technical requirements

      
Quality Different Sizes FFUs Refer To Different Application Scenarios And Technical Requirements for sale

Different Sizes FFUs Refer To Different Application Scenarios And Technical Requirements Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Shenzhen Zhong Jian South Environment Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)